The GPI Series 2000 is designed to eliminate high-frequency noise and high-voltage impulses (also known as spikes or surges) from the AC power that runs your electronic equipment.
The power conditioner installs between the power source and the critical load, and because it is a three-phase device, the GPI Series 2000 provides protection for all transformer phases that power a large system.
Sophisticated electronic systems contribute to the profitability of your business, and clean power is an essential element in their reliable operation.
Each electronic system responds to power-quality problems differently, but properly protected systems benefit in a variety of ways. These benefits include fewer hardware failures, fewer no problem found service calls, less system downtime, higher manufacturing yield, better image quality and longer equipment life.
General Specifications
Continuous Capacity 15 kVA
BTU/Hr. Output 1536
Efficiency > 97% (at full load, unity power factor)
Step Load Change + 0.8% (at unity power factor)
Noise Rejection
With unit under power and the isolation transformer configured for a transformation ratio of 1:1 and with an ANSI/IEEE C62.41, Category A pulse applied either normal mode or common mode at the input, the noise output voltage will be less than 10 volts normal mode and less than .5 volts ( of one volt) common mode in all four quadrants(CM-NM, NM-NM, CM-CM, NM-CM).