Square D EX150T3H Transformer, Dry Type, DOE 2016, 150kVA, 3 Phase, 480V Delta Primary, 208Y/120V Secondary, 22K, 150C Rise w/ Panelboard
***Preowned transformer with safety switch interruptor & panelboard. Unit has slight wear from normal use. Buyer can expect the same item pictured with 30-day warranty. See photos for details.
(Please be advised that any warranty/guarantee/return policy provided from the seller is between the buyer and the seller only. Bid on Equipment is not and cannot be held responsible in any way. Please reference our Terms and Conditions for further information.)
New Three-Phase Offering from Square D, DOE 2016 EX Exceed the efficiency levels. The DOE EX are terminals sized to handle wire ranges to match Square D circuit breakers, switches, panelboards, etc. Located to meet NEC bending radius and layout to simplify connections. The IZ Levels will allow for designing with the minimum AIC Panels available. The In-rush current limited to expand the Square D circuit breaker options at both 125 and 250% sizing. This DOE 2016 energy efficient transformer, is a 3 phase, 150 kVA, 60 Hz, with a natural convection cooling. The primary voltage of 480 V delta and a secondary voltage of 208Y/120 V. This transformer has a rated Impedance withstand voltage of 10 kV and a temperature rise of 150 C & 220 C insulated. This product has an ambient air temperature of 40-40 C and an average air temperature of 30 C. It has an efficiency of 99 % and a load factor of 35 % and an ambient air temperature of 75.0 C. With a peak withstand current of 10.0 kA and a tap loss of 210.0 & 3192.0. Dimensions for this product are 16.6 % (H), 1247 mm (W), 723 mm (D) and a weight of 855 mm. This product complies to UL 1561, CSA C22.2 No 47 & NEMA ST-20.
Main
Range of product: Square D
Product or component type: Transformer
Device short name: DOE 2016
Transformer type: Energy efficient
Device application: Low voltage electrical distribution
Complementary
Box number: 22K
Network number of phases: 3 phases
Rated operational power in VA: 150 kVA
Network frequency: 60 Hz
Type of cooling: Natural convection
Primary voltage: 480 V delta
Number of tap-offs: 2 2.5 % FCAN
4 2.5 % FCBN
Secondary voltage: 208Y/120 V
Coil Material: Aluminium
Basic IMP level (BIL): 10 kV
Temperature Rise: 150 C
220 C insulated
DOE Efficiency: 99 % 35 % 167 F (75.0 C)
Sound Level: 47 dB
3 dB NEMA ST-20
%IZ4.20 %
%IX0.036 %
X/R Ratio: 1.69
Let Through Current: 10.0 kA
Transformer Losses: 210.0 no load (core loss)
3192.0 load loss (coil loss)
Transformer BTU/HR: 1016.677571966784 16.6 %
1397.272149 25 %
3439.439136 50 %
6843.050781 75 %
11608.107084 100 %
Height: 49.09 in (1247 mm)
Depth: 28.46 in (723 mm)
Width: 33.66 in (855 mm)
Net weight: 1100.00 lb(US) (498.95 kg)
Mounting support: Floor
Floor, with 7400 FMB
Ceiling, with 7400 CMB22K
Degree of protection UL type 1
UL type 2, with 7400DS22K
UL type 3R, with 7400WS22K
Electrical connection: 4 Hole Nema Pad primary 0.44 in (11.1 mm)
4 Hole Nema Pad secondary 0.44 in (11.1 mm)
6 Hole Nema Pad sec - XO 0.44 in (11.1 mm)
Environment
Ambient air temperature for operation: 104 F (40 C)
Average ambient air temperature for operation: 30 C
Standards: UL 1561
CSA C22.2 No 47
NEMA ST-20
Additional Prep Fees May Apply