Generac Industrial gaseous engine-driven generator, turbocharged/aftercooled 12 cylinder 21.9L engine,
consisting of the following features and accessories:
• Stationary Emergency-Standby rated
• 400 kW Rating, wired for 277/480 VAC three phase, 60 Hz
• Power Manager Digital Control Platform for Generac Modular Power System's Paralleling Controller
• Standard Weather Protective Enclosure, Steel, Industrial Grey Baked-On Powder Coat Finish
• UL2200
• Power Zone Digital Control Panel for Single Generators - Meets NFPA 99 and 110 requirements
• 21 Light Remote Annunciator Panel – Surface/Flush Mount
• Remote Emergency Stop Switch, Break-Glass, shipped loose
• 225 AH, 1155 CCA Group 8D Batteries, with rack, installed
• Battery Charger, 10 Amp, NFPA 110 compliant, installed
• Coolant Heater, 2500W, 240VAC
• 120V GFCI and 240V Outlet
• Flex Fuel Line
• Oil Temp Sender
• 600 Amp MLCB, 80% rated thermal-magnetic
• MG0400KG30219S18PPYYG
Additional Prep Fees May Apply